Hardware modules
Modules serve two roles in SignalSQL: some are drivers that interface the
engine with a specific electrical interface or protocol, and others implement
algorithms or logical functions. Each module presents itself as one or more
tables; the signals it exposes show up in the built-in
INPUT/OUTPUT tables, and you enable or
disable modules through the MODULES table.
The bundled modules are OWSERVER, GPIO, PID, SLOW_PWM, and LOGGER, statically linked into the engine. To add hardware beyond these, SignalSQL runs out-of-process drivers you declare in the config file — no recompiling.
OWSERVER — 1-wire
Connects SignalSQL to a one-wire server (owserver, from OWFS). Add a
connection by inserting a row into the OWSERVER table with the server’s host:
CREATE TABLE OWSERVER (
ID INT AUTO_INCREMENT PRIMARY KEY, -- The id of the OWSERVER record
Host VARCHAR(255), -- IP address or hostname owserver runs on
Port INT, -- Port. If NULL or zero, the default 4304 is used
Status VARCHAR(255) -- Connection status:
-- INIT|CONNECTING|CONNECTED|ERROR
);
Once connected, SignalSQL queries the owserver for all attached devices and adds
a row to the OWDEVICE table for each:
CREATE TABLE OWDEVICE (
ID VARCHAR(255) PRIMARY KEY, -- The physical id of this device
OwServer INT, -- The id of the OWSERVER for this device
Type VARCHAR(255) -- Device type:
-- SERIAL_NUMBER|SWITCH|THERMOMETER|
-- AD_CONVERTER|BATTERY_MONITOR|RTC
);
- ID is the unique physical ID reported by the unit.
- OwServer references a row in
OWSERVER. - Type describes the device.
Most devices in OWDEVICE are also represented in INPUT or OUTPUT, where the
row Name takes the form owdevice:{id} — so a thermometer becomes a readable
INPUT signal you can reference with =INPUT/owdevice:{id}/Value.
PID — closed-loop control
Implements the PID (Proportional-Integral-Derivative) control algorithm: it holds a process at a setpoint by continuously adjusting an output to minimise the error between the setpoint and the measured value.
CREATE TABLE PID (
ID INT AUTO_INCREMENT PRIMARY KEY, -- The id of this PID instance
INPUT double REFERENCE, -- The input signal
SETPOINT double REFERENCE, -- The desired value
Kp double, -- The proportional gain
Ki double, -- The integral gain
Kd double, -- The derivative gain
Direction TINY, -- Direction of the output
OUTPUT double REFERENCE -- The output of the PID algorithm
);
The output is Kp·P + Ki·I + Kd·D, where P responds to the present error,
I eliminates sustained steady-state error, and D dampens the response to
prevent overshoot. Tuning Kp/Ki/Kd trades off stability, responsiveness,
and overshoot.
INPUT, SETPOINT, and OUTPUT are reference columns — they point at rows
in other tables — so a loop is composed entirely from existing signals:
INSERT INTO PID (INPUT, SETPOINT, Kp, Ki, Kd, Direction, OUTPUT)
VALUES (
'=INPUT/owdevice:28.F049AF040000/Value', -- measured temperature
'=setpoints/hlt/Value', -- your target row
2.0, 0.5, 1.0, 1,
'=OUTPUT/owdevice:12.574B7D000000/Value' -- element / relay
);
LOGGER — sampling to a table
Periodically samples a referenced value and records it, so you can build history and charts (point Grafana at the resulting table). Configure a logger by inserting a row naming what to sample and how often:
-- id, name, interval (ms), ..., source reference
INSERT INTO logger VALUES (1, 'hlt', 1000, 3, '=INPUT/owdevice:28.F049AF040000/Value');
GPIO — digital I/O
Reads digital inputs and drives digital outputs on the host’s GPIO pins
(for example, Raspberry Pi). The pins it manages appear as digital (Type = 'D')
signals in the INPUT and OUTPUT tables, where you read or drive them like any
other signal.
SLOW_PWM — time-proportioned output
Turns a continuous 0–100% control value into a slow on/off duty cycle, so a
plain relay or solid-state relay can modulate power to a resistive load like a
heating element. It time-proportions the output over a sample window — a higher
percentage keeps the output on for a larger fraction of each window. Point it at
a control value (for example a PID output) as its
input and at a digital OUTPUT signal as its output.
Custom hardware: out-of-process drivers
Beyond the built-in modules, you can add hardware by configuration with an
out-of-process driver. A driver is a separate program that connects to the engine
and presents itself as a virtual SQL table; its rows publish into INPUT, so a
=driver/row/column reference resolves to a
live reading exactly as a built-in module does. Because a driver runs in its own
process, a slow or crashing driver can’t stall or crash the engine.
Declare each driver in its own [Driver <name>] section of the
config file:
[Driver relays]
Exec = serialdrv
Args = --config relayboard.conf
Enabled = true
| Option | Meaning |
|---|---|
Exec | The driver executable. A bare name (no path) is resolved next to the engine binary in bin/, so a shipped driver needs no path; an explicit relative or absolute path is used as-is. |
Args | Extra command-line arguments passed to it (whitespace-separated). |
Enabled | true (default) spawns the driver at startup; false declares it without starting it. |
The driver runs with the config file’s directory as its working directory, so
a relative --config relayboard.conf resolves next to signalsql.conf — where
the shipped driver sample configs are installed.
SignalSQL supervises declared drivers: it launches them at startup, restarts a
crashed driver with backoff, and reaps one that has gone silent. When a driver
disconnects its table and published INPUT rows are removed, so nothing serves
stale values. Tuning options (DriverPort, DriverPing, DriverDead) live in
the [Server] section.
Actuator writes
A driver column declared as an output is written by a SQL UPDATE: updating it
sends the new value to the device — the write half of a control loop. So the same
UPDATE relays SET relay1 = 1 that changes a row also switches the physical relay.
Serial devices (RS232)
SignalSQL ships a generic, data-driven serial driver — serialdrv — for the
common case of relay boards and simple serial sensor modules. It binds a serial
device to a SQL table entirely from a config file: no scripting, no compiling, and
one binary serves many devices — each device is just another config file. The
serialdrv binary installs next to the engine in bin/, with a ready-to-edit
sample relayboard.conf beside the main config file:
- Linux:
/etc/opt/signalsql/relayboard.conf - Windows:
C:\ProgramData\Centlake\SignalSQL\etc\relayboard.conf
Point a [Driver] section at it to bring it online, then restart the service:
# signalsql.conf
[Driver relayboard]
Exec = serialdrv ; a bare name is found next to the engine binary
Args = --config relayboard.conf ; resolved in the config dir, where the sample installs
The device config file
INI-style, one file per device. A minimal relay board:
[serial]
port = COM3 ; /dev/ttyUSB0 on Linux
baud = 9600
[table]
name = relays ; the SQL table this device presents
key = board1 ; the row identity (column 0)
[output relay1] ; one OUTPUT column per channel
on = A0 01 01 A2 ; whitespace-separated hex to switch it on
off = A0 01 00 A1 ; ...and off
[output relay2]
on = A0 02 01 A3
off = A0 02 00 A2
This presents the table main.relays with a Name identity column and two
actuator columns. Drive the relays over the MySQL protocol:
UPDATE relays SET relay1 = 1 WHERE Name = 'board1'; -- sends A0 01 01 A2
UPDATE relays SET relay1 = 0 WHERE Name = 'board1'; -- sends A0 01 00 A1
A written value is truthy → on, zero or NULL → off, so 1/0,
TRUE/FALSE, or any nonzero number all work. Each channel is a column, so
an 8-relay board is one row with eight [output] sections and a single UPDATE
can switch several at once. Because the on/off byte strings are listed literally,
any checksum they carry (here A2 = A0 + 01 + 01) is already baked in — there is
nothing else to compute.
Where the port lives
The port value selects one of three backends:
port = | Talks to |
|---|---|
COM3 / /dev/ttyUSB0 | a real serial port (8N1) |
tcp:host:port | a networked serial device server (ser2net, Moxa/USR converters, …) |
file:<path> | a dry-run sink — appends the wire bytes to a file instead of a real port (write-only), handy for checking exactly what an UPDATE sends |
Reading device state back
A device you can query is described with [input <name>] sections. Each poll
interval the driver sends query, matches the reply against the response regex,
and streams capture group 1 back as a live reading on a column you can SELECT:
[input temp]
type = double ; double (default) | int | bool
poll = 1000 ; ms between polls
query = "READ\r" ; bytes to send (C escapes: \r \n \t \xHH)
response = TEMP=([0-9.]+) ; regex; capture group 1 is the value
# map = on=1, off=0 ; optional: map matched text to a value
SELECT temp FROM relays WHERE Name = 'board1'; -- the last polled reading
A board can mix [output] and [input] sections — each becomes a column on the
same row. Inputs need a readable backend (a real port or tcp:; the file: sink
is write-only). If a poll gets no matching reply, the previous value stays in
place.
The driver reads its config when SignalSQL spawns it, so restart the service after editing a device config.